Co-optimization of capacitor placement and generator voltage control using advanced BFOA for active power loss reduction under extreme load levels

Anh Tuan Bui, Tien Dung Nguyen, Tung Tran

Abstract


Optimal reactive power dispatch (ORPD) is a critical tool for maintaining the efficiency and security of modern power systems. This paper addresses the ORPD problem under highly stressed grid conditions (130% loading) by proposing a comprehensive co-optimization framework. The framework simultaneously optimizes discrete shunt capacitor capacities and continuous generator terminal voltages using an advanced bacterial foraging optimization algorithm (BFOA) integrated with a time-varying dynamic step-size strategy. The methodology is validated on the IEEE 14-bus system and compared against standard particle swarm optimization (PSO). Simulation results demonstrate that the proposed BFOA achieves a superior active power loss reduction of 23.502% (from 28.067 MW to 21.470 MW) and effectively eliminates all generator reactive power (Qg) violations. The findings highlight the importance of joint co-optimization in achieving global grid efficiency under extreme operational scenarios.

Keywords


BFOA; Co-optimization; ORPD; Power loss; Stressed grid;



DOI: http://doi.org/10.11591/ijeecs.v44.i1.pp9-21

Refbacks

  • There are currently no refbacks.


Creative Commons License
This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.

Indonesian Journal of Electrical Engineering and Computer Science (IJEECS)
p-ISSN: 2502-4752, e-ISSN: 2502-4760
This journal is published by the Institute of Advanced Engineering and Science (IAES).

shopify stats IJEECS visitor statistics